Difference between revisions of "Information Systems:Building Power"
m (→Notes) |
m |
||
Line 16: | Line 16: | ||
[[File:Model-SN-Numbers-For-EatonUPS.jpg|400px]] |
[[File:Model-SN-Numbers-For-EatonUPS.jpg|400px]] |
||
+ | ==IS Web Card on Liebert UPS== |
||
− | ==Notes== |
||
− | + | The Liebert Nfinity UPS uses an IS (IntelliSlot) Web Card. This is an add-on card to provide network connectivity to the UPS (e.g. email alerts, SNMP monitoring, and a web interface). This card was installed on April 29, 2021 after the older OpenComms Web Card (OCWEBCARD) started to constantly restart. This "agent" (as Liebert terms it) can be restarted separately from the UPS. It interfaces with the UPS via a control board, and this communication has proven (although just once) to break at times, for which the fix was to have a Liebert field agent come and restart the UPS (put it into bypass mode). |
|
+ | Zabbix polls this agent via SNMP - both voltage and battery stats can be viewed. |
||
[[Category: Power, Alarms, and Monitoring]] |
[[Category: Power, Alarms, and Monitoring]] |
Revision as of 17:56, 29 April 2021
Overview
The attached JPG is a diagram of how electric power is organized in the Server room. The rack closest to the door and the middle rack are fed power from the Liebert UPS which filters power from Hydro or in the event of a Hydro failure, the generator. The rack farthest from the door containing the Power8 hardware has 2 different power feeds, one from the Liebert UPS and the other straight from Hydro. The second feed from Hydro plugs into the Power8 UPS at the bottom of that rack. The Power8 rack has each of its 2 feeds of power protected by a UPS so even if 1 UPS fails or drains, the other UPS will still provide electricity so that the Power8 will remain up. The only way that the Power8 system will go down is if both UPS's fail AND we have Hydro AND generator failure. Highly unlikely. The technical support number and account information for Liebert is on the top right side of the UPS.
Support for Liebert UPS * Support phone number: 1-800-543-2378 * Support phone number (direct): +1-800-222-5877 (ext 2 for Liebert, ext 2 for Geist) * Device model: Nfinity Power System * Device serial number: 0635501111001G1 * Liebert Unit Tag Number: 1375377 (Provide this during a support call, it's faster) Support for Eaton UPS * 1-800-356-5737
IS Web Card on Liebert UPS
The Liebert Nfinity UPS uses an IS (IntelliSlot) Web Card. This is an add-on card to provide network connectivity to the UPS (e.g. email alerts, SNMP monitoring, and a web interface). This card was installed on April 29, 2021 after the older OpenComms Web Card (OCWEBCARD) started to constantly restart. This "agent" (as Liebert terms it) can be restarted separately from the UPS. It interfaces with the UPS via a control board, and this communication has proven (although just once) to break at times, for which the fix was to have a Liebert field agent come and restart the UPS (put it into bypass mode).
Zabbix polls this agent via SNMP - both voltage and battery stats can be viewed.